SF6 Gas Analyzer: Purity, Moisture and Decomposition Testing
An SF6 gas analyzer checks the condition of SF6 in switchgear and gas-insulated equipment. Wrindu, based in Shanghai, supplies purity, moisture and decomposition testing instruments for substation work, with configurations matched to the compartment and readings you need.
- Warranty
- 12-month warranty

What an SF6 Gas Analyzer Measures and How to Specify a Unit
An SF6 gas analyzer checks the condition of SF6 gas in switchgear and other gas-insulated equipment. It measures purity or concentration, moisture content expressed as dew point, and decomposition by-products such as SO2, H2S and CO. Purity supports dielectric strength and arc-quenching performance, moisture control protects insulation and limits corrosion, and decomposition readings show whether arcing or overheating has altered the gas. Wrindu, the brand of Rui Du Mechanical and Electrical (Shanghai) Co., Ltd., specializes in power testing equipment. Send compartment details, gases to be measured and site conditions through the inquiry form so the right configuration can be proposed.
An SF6 gas analyser is the same instrument as an SF6 gas analyzer; “analyser” is the British spelling, and both describe the same product category. When requesting a quotation, include equipment voltage class and gas compartment type, the readings needed—purity, moisture or decomposition products—whether the unit must be carried between bays, ambient and site conditions, and reporting needs. Use the inquiry form or sales email. Specifications are confirmed against the exact Wrindu model quoted.

SF6 gas tester, view 2 
SF6 gas tester, view 3
SF6 gas analyzer models and specifications
| Model | RDZH-709 A | RDZH-709B |
|---|---|---|
| Dew point detection module | Dew point detection module | |
| Dew point range | ―80℃ ~ +20℃ | |
| Measurement accuracy | ±0.5℃ | |
| Micro water range | 0.05 ~ 23100 μL/L | |
| Measurement response time(+20℃) | -80℃ →20℃ 5s(63%),45s(90%) 20℃→-80℃ 10s(63%),240s(90%) | |
| Resolution | Dew point:0.1℃ Micro water:0.1ppm(100ppm ~ 1000ppm) 0.01ppm (10ppm ~ 100ppm) | |
| Repeatability | ±0.2℃ | |
| Purity detection module | Purity detection module | |
| Measurement range | 0~99.99% | |
| Measurement accuracy | ±0.2% | |
| Repeatability | ±0.1% | |
| Resolution | 0.01% | |
| Decomposition product detection module | Decomposition product detection module | |
| Measurement range | SO2:0 ~ 100μL/L H2S:0 ~ 100μL/L CO: 0 ~ 1000μL/L | SO2:0 ~ 100μL/L H2S:0 ~ 100μL/L CO: 0 ~ 1000μL/L HF: 0 ~ 10μL/L |
| Measurement accuracy | SO2 : when the measured value ≤10μL/L, the error±0.2μL/L when the measured value≥10μL/L, the error≤±3% H2S : when the measured value≤10μL/L, the error±0.2μL/L when the measured value≥10μL/L, the error≤±3% CO: when the measured value≤50μL/L, the error±0.5μL/L when the measured value≥50μL/L, the error≤±4% | SO2 : when the measured value ≤10μL/L, the error±0.2μL/L when the measured value≥10μL/L, the error≤±3% H2S : when the measured value≤10μL/L, the error±0.2μL/L when the measured value≥10μL/L, the error≤±3% CO: when the measured value≤50μL/L, the error±0.5μL/L when the measured value≥50μL/L, the error≤±4% HF: the error of measured value≤±0.1μL /L |
| Repeatability | SO2 : when the measured value≤10μL/L,the repeatability≤±0.1 when the measured value≥10μL/L,the repeatability≤±2% H2S : when the measured value≤10μL/L,the repeatability≤±0.1 when the measured value≥10μL/L,the repeatability≤±2% CO: when the measured value≤50μL/L,the repeatablity±0.3 when the measured value≥50μL/L,the repeatability≤±3% | SO2 : when the measured value≤10μL/L,the repeatability≤±0.1 when the measured value≥10μL/L,the repeatability≤±2% H2S : when the measured value≤10μL/L,the repeatability≤±0.1 when the measured value≥10μL/L,the repeatability≤±2% CO: when the measured value≤50μL/L,the repeatablity±0.3 when the measured value≥50μL/L,the repeatability≤±3% HF: the repeatability of measured value≤±0.1 |
| Resolution | 0.1μL/L | |
| Other parameters | Other parameters | |
| Gas flow | Flow regulation A regulated at 0.2l/min Flow regulation B regulated at 0.5-0.6l/min | |
| Probe protection | stainless steel sintered filter screen | |
| Working environment | Temperature -10℃ ~ +50℃ Humidity 0 ~ 90%RH |
| Parameter | Value | |
|---|---|---|
| technical requirement | ||
| 1 | Compressor requirements | Customized 30 cubic meters per hour SF6 high-pressure oil-free compressor |
| 2 | vacuum pump | 64 cubic meters per hour, maximum vacuum ≤10pa |
| 3 | Requirements for vacuum compressors | Vacuum recovery compressor 20 cubic meters per hour, recovery final pressure<0.5mbar |
| 4 | Liquid storage tank | 350L/50bar liquid storage tank;Built in refrigeration system. |
| 5 | Dry filter | It adopts vacuum activation function, and the filter element can be replaced without disassembly |
| 6 | Particle filter | have |
| 7 | pressure display | Display unit: Mpa, both recovery final pressure and vacuum final pressure can be set |
| 8 | External hose | 5-meter or optional 10-meter trachea with DN20 self -sealing joints at both ends |
| 9 | instructions | English operating manual |
| 10 | working voltage | 415V/AC50Hz |
| 11 | Touch Screen | 15inch touch screen, directly displaying parameters and flowcharts |
| Parameter | Value |
|---|---|
| Picture | |
| Model | RDCD-707 |
| Name | Technical parameters |
| Measuring range | 0 ~ 100% |
| Measurement accuracy | ±0.1% |
| Repeatability | ±0.05% |
| Resolution | 0.01% |
| Sampling flow | 0.2L/min |
| Measuring time | ≤30S |
| Working environment | Temperature-10℃ ~ +50℃,humidity0 ~ 90%RH |
| Working power supply | Lithium battery power supply, AC and DC dual-use, automatic switching, overcharge and over-discharge protection function |
| Volume and weight | 358×240×108(mm), weighing about 3.6 kg |
| Parameter | Value |
|---|---|
| Picture | |
| Model | RDCDF-706 |
| Measuring range | purity: 0 to 100% |
| Accuracy | purity: ± 1% |
| Resolution | purity: 0.1% |
| Repeatability | purity: ± 0.5% |
| Pressure range | 0 ~ 1MPa |
| Gas flow rate | 0.3 ~ 0.4L / min |
| Measuring time | 5 minutes |
| Operating voltage | 110 ~ 220VAC, AC and DC |
| Storage temperature rating | -25 ~ + 70 ℃ |
| Operating environment | temperature: -25 ~ + 60 ℃ |
| Power supply | lithium battery, AC and DC dual-use, automatic switching, overcharge, and over-discharge protection lithium battery, AC and DC dual-use, automatic switching, overcharge and over-discharge protection |
Choosing an SF6 Gas Analyzer for GIS, Circuit Breakers and Gas Compartments
Selection starts with the switchgear type and compartment arrangement. A GIS bay, a circuit breaker and other gas-insulated equipment can differ in access, gas volume and the readings that matter. Decide whether purity, moisture and decomposition products are all required or only part of the set. If the tester will move between bays, consider weight, carrying method and power source. Reporting needs shape the display, data storage and export functions. These are general selection points; the exact features and ranges are confirmed for the Wrindu model quoted. For related diagnostics, circuit breaker analyzers and partial discharge test equipment address different checks.
The RDQH-64/350WF is designed for SF6-filled electrical equipment such as GIS, circuit breakers and other high-voltage switchgear. The SF6 multifunctional tester is equipped with imported sensors for measuring humidity, purity and various gases such as SO2, H2S, CO and HF. Other model names shown in the specification tables on this page are RDZH-709 A and RDZH-709B. Each model should be considered against its own stated application and readings, not as a general claim for the range.
Wrindu has over 10 years of professional experience in global market service and has exported products to more than 120 countries, with main markets in South Asia, Southeast Asia and Africa. Rui Du Mechanical and Electrical (Shanghai) Co., Ltd. was established in 2014. During the 12-month warranty, Wrindu provides free training, manuals, complaint response and software upgrades. Its after-sales team offers installation, training and maintenance support, and maintenance and spare parts remain available after the warranty. OEM and ODM customized products are provided, and many listings show a minimum order of 1 set. T/T and PayPal are accepted in USD or CNY, with FOB and express delivery.
The normal order sequence is straightforward: send the test object, voltage level and tests needed; receive a selection proposal; place the order; complete pre-delivery inspection and packing; arrange shipping; and take part in training. The quoted Wrindu model remains the reference for the configuration supplied.
How an order runs
- Send your requirements
- The equipment you need to test, its voltage level and the tests you plan to run.
- Selection and quotation
- Wrindu proposes matching tester models and accessories and sends a quotation.
- Inspection and delivery
- Equipment is inspected and packed before delivery; the delivery time is confirmed with the quotation.
- Warranty and training
- During the 12-month warranty, Wrindu provides free training, manuals, complaint response and software upgrades.
Request a quotation
Send the test object and voltage level; we will propose matching tester models.
Or write to sales@hipottestequipment.com