Insulation Resistance Tester Selection for Utilities and Contractors
An insulation resistance tester applies a test voltage and measures insulation resistance, showing the condition of cables, motors, transformers and switchgear. Wrindu supplies these testers from Shanghai to utilities and contractors.
- Warranty
- 12-month warranty

Selecting an Insulation Resistance Tester for Cables, Motors and Switchgear
An insulation resistance tester applies a test voltage across insulation and measures the resistance that results, so a reading shows whether insulation is sound or deteriorating. Utilities and contractors use it on cables, motors, transformers and other electrical equipment before commissioning, after repair and during periodic maintenance. Wrindu is the brand of Rui Du Mechanical and Electrical (Shanghai) Co., Ltd., a Shanghai company specializing in power testing equipment.
Selection starts with the test object and the tests required, not with the model list. Model pages for the RD3200E, RD3202E, RD3205E, RD3210E and RD3215E describe each unit, and the specification tables on this page show their parameters. Send the test object, voltage level and tests needed through the contact form; Wrindu replies with a selection proposal.

Insulation resistance tester, view 2 
Insulation resistance tester, view 3
Insulation resistance tester models and specifications
| Parameter | Value |
|---|---|
| Item | Description |
| Insulation resistance range | 0 ~ 20.0TΩ |
| Insulation resistance resolution | 0.01kΩ @0 ~ 9.99kΩ 0.1kΩ @10.0 ~ 99.9kΩ; 1kΩ @100 ~ 999kΩ 10kΩ @1.00 ~ 9.99MΩ; 100kΩ @10.0 ~ 99.9MΩ 1MΩ @100 ~ 999MΩ; 10MΩ @1.00 ~ 9.99GΩ 100MΩ @10.0 ~ 99.9GΩ; 1GΩ @100 ~ 999GΩ 10GΩ @1.00 ~ 9.99TΩ; 100GΩ @10.0 ~ 20.0TΩ |
| Full scale resistance value (R FS ) in different rate output voltages | 200GΩ @100V; 500GΩ @250V; 1.00TΩ @500V; 2.00TΩ @1000V; 5.00TΩ @2500V; 10.0TΩ @5000V; 20.0TΩ @10000V |
| Insulation resistance accuracy in different rate output voltages | ±5% @ R<1/10R FS ; ±20% @ 1/10R FS ≤R≤R FS |
| Rate output voltage | 100V, 250V, 500V, 1000V, 2500V, 5000V, 10000V |
| Custom setting output voltage | 50~10000V, minimum step is 10V, and when controlling by rotating mouse, the step switches between 10V, 100V, 200V according to the speed. |
| Output voltage accuracy | 0% ~ 10% |
| Short circuit current | Adjustable 1~ 6mA, step 1mA. Accuracy ± 5% |
| Continuous output power | 55W |
| Measurement accuracy of output voltage | ±(2%±3dgt) |
| Voltage measurement | Voltage rang: AC/DC 10V ~ 660V; Accuracy: ±(2%±3dgt) AC voltage frequency rang: 25 ~ 85Hz; Accuracy: ±0.2Hz; Resolution: 0.1Hz |
| Capatiance measurement | Range: 10nF ~ 25μF (test voltage ≥100V); Accuracy: ±10% ± 5nF |
| Custom setting test time | 10s ~ 99min adjustable |
| Power supply | AC power supply: 85-264Vrms, 50/60Hz, 65VA Built in battery: 16.8V/4400mAh lithium battery Built in charger: 16.8V/2.3A, maximum charging time limit of 5 hours Battery life: 10kV@100M Ω load, approximately 5 hours |
| Operating conditions | Temperature -10 ~ 50℃; Relative humidity<90%, no condensation. |
| Port | RS232 (optional RS485), USB (U-disk supports FAT or FAT32 formats) |
| Model | RD3200E | RD3202E |
|---|---|---|
| Picture | ||
| Rated Voltage | 50V, 250V, 500V, 1kV, 2.5kV, 5kV | 50V, 250V, 500V, 1kV, 2.5kV, 5kV, 10kV |
| Insulation Resistance Range | 0.005MΩ ~ 5.00TΩ | 0.005MΩ ~ 10.00TΩ |
| Custom Setting Output Voltage | 40V ~ 5kV | 40V ~ 10kV |
| Function | Insulation resistance (IR), polarization index (PI), dielectric absorption ratio (DAR), step voltage (STEP), ramp (RAMP), and voltage measurement (V). | |
| Power Supply | Rechargeable lithium battery pack 5.2Ah/14.8V | |
| Output Voltage Accuracy | (5% ~ 10%) ±10V | |
| Short Circuit Current | 5mA Max | |
| Voltage Measurement | Rang: DC 0V~1000V; Accuracy: ± 5% rdg ± 3V Rang: AC 0V~700V; Accuracy: ± 5% rdg ± 3V | |
| Customs Setting Test Time | 10s ~ 3600s | |
| Real-Time Current Display | Display test current value, current range: 0.001nA ~ 5 mA | |
| Real-Time Voltage Display | Real-time monitoring of the voltage of the measured terminal. When the voltage exceeds 36V, testing will automatically be prohibited to effectively protect the instrument and the operator. | |
| Test Timer | Automatic record test time, time range: 0s ~ 9999s. | |
| Storage Function | Automatically store the test data of 1000 groups, which can display, replay, and store test records. | |
| USB Communication | Yes, upload the test record to the PC using a USB cable. | |
| Bluetooth Communication | It can connect to Android mobile phones or other devices with Bluetooth. | |
| Battery Power Indication | With the battery power indication, when the battery voltage is low, it will remind you to charge in time. | |
| Automatic Shutdown | After 15 minutes, the startup will shut down automatically without any operation. | |
| Working Environment | -20℃ ~ 50℃; 80% RH | |
| Withstand Voltage | AC 3kV 50Hz 1min (between the test circuit and shell) |
| Parameter | Value | |
|---|---|---|
| Measurement range | Resistance measurement range | Accuracy |
| 20MΩ | 0.01~19.99MΩ | ±(5%+3d) |
| 200MΩ | 5.0~199.9MΩ | ±(5%+3d) |
| 2GΩ | 0.05~1.999GΩ | ±(5%+3d) |
| 20GΩ | 0.5~19.99GΩ | ±(5%+3d) |
| 200GΩ | 5.0~199.9GΩ | ±(10%+3d) |
| 2000GΩ | 50~1999GΩ | ±(20%+10d) |
| Model | RD3205E | RD3210E | RD3215E |
|---|---|---|---|
| Picture | |||
| Rated Voltage | 50V, 250V, 500V, 1kV, 2.5kV, 5kV | 50V, 250V, 500V, 1kV, 2.5kV, 5kV, 10kV | 50V, 250V, 500V, 1kV, 2.5kV, 5kV, 10kV, 15kV |
| Insulation Resistance Range | 0.005MΩ ~ 10.0TΩ | 0.005MΩ ~ 20.0TΩ | 0.005MΩ ~ 30.0TΩ |
| Custom Setting Output Voltage | 40V ~ 5kV | 40V ~ 10kV | 40V ~ 15kV |
| Power Supply | Rechargeable lithium battery pack 6.2Ah/14.8V | ||
| Output Voltage Accuracy | (5% ~ 10%) ±10V | ||
| Short Circuit Current | 7mA | ||
| Capacitance Measurement | Range: 10nF ~ 200μF; Accuracy: ±10% rdg ± 10nF | ||
| Voltage Measurement | Rang: DC 0V~1000V; Accuracy: ±5% rdg ± 3V Rang: AC 0V~700V; Accuracy: ±5% rdg ± 3V | ||
| Custom Setting Test Time | 10s ~ 3600s | ||
| Real-Time Current Value | Display test current value, current display range: 0.001nA ~ 7.5mA | ||
| Real-Time Voltage Value | Automatically monitor the voltage of the measured object. When the voltage exceeds 36V, the test will be automatically prohibited to effectively protect the instrument and the operator. | ||
| Test Timer | Automatically record test duration, timing range: 0s ~ 9999s. | ||
| Store Function | Automatically store the test date, time, and timing. There are a total of 1000 groups that can view and replay the stored test record. | ||
| USB Communication | Yes, upload the test record to the PC using a USB cable. | ||
| Bluetooth Communication | Yes, it can connect to Android mobile phones or other devices with Bluetooth communication. | ||
| Battery Power Indication | With the battery power indication, when the battery voltage is low, it will remind you to charge in time. | ||
| Automatic Shutdown | After 15 minutes, the start-up will shut down automatically without any operation. | ||
| Working Environment | -20℃ ~ 50℃; 80% RH | ||
| Withstand Voltage | AC 3kV 50Hz 1min (between the test circuit and shell) |
What Does an Insulation Resistance Tester Measure?
An insulation tester is the short term for an insulation resistance tester, and the two names describe the same instrument, which checks insulation condition by applying a voltage and reading resistance. Wrindu’s digital insulation resistance tester is widely used in resistance value testing of various insulation materials and in insulation resistance measurement of transformers, motors, cables and electrical equipment.
The category covers portable digital units and higher-voltage instruments, and model details sit on the named Wrindu product pages. On this page, the specification tables for the RD3200E, RD3202E, RD3205E, RD3210E and RD3215E show the listed parameters of each model.
How Is an Insulation Resistance Test Performed?
Testing follows a fixed order: isolate the equipment and prepare it, connect the test leads, apply the selected test voltage, then read the insulation resistance and record the results. Test voltage is chosen to suit the equipment, and readings are taken once the value settles. The spot reading, time resistance and step voltage methods are the three commonly used approaches; the method follows the equipment and the test objective.
Insulation resistance is a measurement of how well insulation opposes current flow between conductors and ground. Low or falling readings point to moisture, contamination, damage or aging, and readings taken over time support maintenance decisions on cables, motors and transformers. A downward trend matters as much as a single value, so each result is recorded with the conditions of the test.
Digital Insulation Testers and Insulation Resistance Meters
An insulation resistance meter is built to apply a test voltage and measure very high resistance values, while a general multimeter serves lower-voltage measurements of voltage, current and continuity. The two instruments answer different questions, and a multimeter does not replace an insulation test. Wrindu supplies digital insulation testers whose specifications appear in the tables on this page.
- Which test voltages the insulation system requires
- The resistance range needed for the equipment being tested
- How the unit is powered and how long it runs in the field
- What the display shows and how it reads in daylight
- Which test sequences the instrument runs
- Whether timed tests and data storage are needed
A digital insulation resistance tester is used for checking insulation condition on cables, motors, transformers, switchgear panels and other electrical equipment. On this page, the specification tables show what each listed Wrindu model provides, and the model pages describe the individual units.
When Should You Choose a High Voltage Insulation Tester?
A high voltage insulation tester is chosen when the insulation system needs a higher test voltage than a standard insulation tester provides. Selection depends on the rated voltage of the equipment and the applicable test standard. Typical applications are cables, transformers, motors and switchgear, where insulation is stressed in service and monitored between maintenance intervals.
The RD3215E is a high performance high voltage insulation resistance tester with strong anti-interference performance for testing large high-voltage equipment and substation transmission lines. The RD3205E and RD3210E are also listed in the specification table on this page. Where insulation strength is checked at power frequency, see Hipot testers.
Megohmmeter Insulation Tester: What It Is and When to Use It
A megohmmeter is an insulation tester that measures very high resistance values by sending a high voltage signal into the object being tested. Megohmmeters provide a quick and easy way to determine the condition of the insulation on wire, generators and motor windings, so they are often used as a first check before more detailed diagnostic testing.
Model-specific ranges and functions sit on the named Wrindu product pages, and the specification tables on this page list the parameters of each model. Transformer insulation work is covered by transformer test equipment, and grounding checks by ground resistance testers.
How an order runs
- Send your requirements
- The equipment you need to test, its voltage level and the tests you plan to run.
- Selection and quotation
- Wrindu proposes matching tester models and accessories and sends a quotation.
- Inspection and delivery
- Equipment is inspected and packed before delivery; the delivery time is confirmed with the quotation.
- Warranty and training
- During the 12-month warranty, Wrindu provides free training, manuals, complaint response and software upgrades.
Request a quotation
Send the test object and voltage level; we will propose matching tester models.
Or write to sales@hipottestequipment.com